228 Actual signals and parameters
.
-
3419 OUTPUT3
UNIT
Selects the unit for the displayed signal selected by
-
.
-
3420 OUTPUT3 MIN Sets the minimum display value for the signal selected by
. See parameter
-
x…x
Setting range depends on parameter
setting.
-
3421 OUTPUT3
MAX
Sets the maximum display value for the signal selected by
See parameter
-
x…x
Setting range depends on parameter
setting.
-
35 MOTOR TEMP
MEAS
Motor temperature measurement. See section
temperature measurement through the standard I/O
.
3501 SENSOR
TYPE
Activates the motor temperature measurement function and
selects the sensor type. See also parameter group
NONE
The function is inactive.
0
1 x PT100
The function is active. The temperature is measured with
one Pt100 sensor. Analog output AO feeds constant current
through the sensor. The sensor resistance increases as the
motor temperature rises, as does the voltage over the
sensor. The temperature measurement function reads the
voltage through analog input AI1/2 and converts it to
degrees centigrade.
1
2 x PT100
The function is active. Temperature is measured using two
Pt100 sensors. See selection
.
2
3 x PT100
The function is active. Temperature is measured using three
Pt100 sensors. See selection
.
3
All parameters
No.
Name/Value
Description
Def/FbEq