220 Actual signals and parameters
32 SUPERVISION
Signal supervision. Supervision status can be monitored
with relay or transistor output. See parameter groups
and
.
3201 SUPERV 1
PARAM
Selects the first supervised signal. Supervision limits are
and
.
Example 1
: If
Case A
value is set to
. Relay energizes when value of the signal selected
with
exceeds the supervision limit
. The relay remains
active until the supervised value drops below the low limit
.
Case B
value is set to
. Relay energizes when value of the signal selected
with
drops below the supervision
limit defined by
. The relay remains
active until the supervised value rises above the high limit
103
All parameters
No.
Name/Value
Description
Def/FbEq
t
t
t
HI par.
Value of supervised parameter
LO par.
Energized (1)
Energized (1)
0
0
Case A
Case B