108 Application macros
Hand/Auto macro
This macro can be used when switching between two external control devices is
needed. To enable the macro, set the value of parameter
5 (
).
For the parameter default values, see section
Default values with different macros
on
. If you use other than the default connections presented below, see section
on page
.
Note:
Parameter
must remain in the default setting 0 (
).
Default I/O connections
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency reference (Hand)
: 0…10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Output frequency reference (Auto)
: 0…20 mA
2)
6
GND
Analog input circuit common
7
AO
Output frequency value
: 0…20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1) (Hand)
13 DI2
Forward (0) / Reverse (1) (Hand)
14 DI3
Hand (0) / Auto (1) control selection
15 DI4
Forward (0) / Reverse (1) (Auto)
16 DI5
Stop (0) / Start (1) (Auto)
X1B
17 ROCOM
Relay output 1
No fault [Fault (-1)]
18 RONC
19 RONO
20 DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
21 DOOUT
22 DOGND
max. 500 ohm
1…10 kohm
1)
1)
360 degree grounding under a clamp.
2)
The signal source must be powered
externally. See the manufacturer’s
instructions. An example of a connection
using a two-wire sensor is given on page
.
Tightening torque: 0.4 N·m (3.5 lbf·in).