276 Actual signals and parameters
DI1
Enables the Interlock function and assigns a digital input
(starting with DI1) to the interlock signal for each PFC relay.
These assignments are defined in the following table and
depend on:
• the number of PFC relays (number of parameters
])
• the Autochange function status (disabled if
= 0.0, and otherwise enabled).
1
All parameters
No.
Name/Value
Description
Def/FbEq
No. of
PFC
relays
Autochange disabled
(Parameter
)
Autochange enabled
(Parameter
)
0
DI1: Speed reg motor
DI2…DI5: Free
Not allowed
1
DI1: Speed reg motor
DI2: First PFC relay
DI3…DI5: Free
DI1: First PFC relay
DI2…DI5: Free
2
DI1: Speed reg motor
DI2: First PFC relay
DI3: Second PFC relay
DI4…DI5: Free
DI1: First PFC relay
DI2: Second PFC relay
DI3…DI5: Free
3
DI1: Speed reg motor
DI2: First PFC relay
DI3: Second PFC relay
DI4: Third PFC relay
DI5…DI5: Free
DI1: First PFC relay
DI2: Second PFC relay
DI3: Third PFC relay
DI4…DI5: Free
4
DI1: Speed reg motor
DI2: First PFC relay
DI3: Second PFC relay
DI4: Third PFC relay
DI5: Fourth PFC relay
DI1: First PFC relay
DI2: Second PFC relay
DI3: Third PFC relay
DI4: Fourth PFC relay
DI5: Free
5
Not allowed
DI1: First PFC relay
DI2: Second PFC relay
DI3: Third PFC relay
DI4: Fourth PFC relay
DI5: Fifth PFC relay