Actual signals and parameters 257
DONE
Reset not requested (normal operation).
0
RESET
Reset energy counters, The value reverts automatically to
1
46 PUMP CLEANING
Set-up of pump cleaning.
4601 PUMP CLEAN
TRIG
Defines how the Pump cleaning function is triggered. The
pump cleaning sequence consists of forward and reverse
“steps”.
WARNING!
Before enabling the Pump cleaning
function, ensure it is safe to perform the pump cleaning
sequence with the connected equipment.
Notes:
The Pump cleaning function overrides parameter
The Pump cleaning function observes the maximum forward
and reverse frequencies (parameters
The Pump cleaning function always uses acceleration time
) and deceleration time 2 (parameter
).
The drive must be ready and its Run enable signal must be
present before the pump cleaning sequence can start.
NOT SEL
No triggering source defined.
0
DI1
Trigger on the rising edge of digital input DI1
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
DI1/SUP1OVR Enable on the rising edge of digital input DI1 or
(parameter
). See
parameter group
7
DI2/SUP1OVR See selection
8
DI3/SUP1OVR See selection
9
DI4/SUP1OVR See selection
10
DI5/SUP1OVR See selection
11
All parameters
No.
Name/Value
Description
Def/FbEq
t
Forward
Reverse