218 Actual signals and parameters
3022 AI2 FAULT
LIMIT
Defines a fault level for analog input AI2. If parameter
, the drive trips on fault
when the analog input signal falls below the set
level.
Do not set this limit below the level defined by parameter
.
0.0%
0.0…100.0%
Value in percent of the full signal range
1 = 0.1%
3023 WIRING FAULT Selects how the drive reacts when incorrect input power and
motor cable connection is detected (ie the input power cable
is connected to the motor connection of the drive).
Note:
Disabling wiring fault (ground fault) may void the
warranty.
DISABLE
No action
0
ENABLE
The drive trips on fault
.
1
3027 OPTION COM
LOSS
Enables the fault
on detecting the
disconnection of MREL-01 relay output extension module
from the drive.
DISABLE
Prevents the fault
even when MREL-01
is disconnected from the drive.
0
ENABLE
MREL-01 is constantly monitored for disconnection and
indicated by the fault
if external relay
outputs are configured.
1
31 AUTOMATIC
RESET
Automatic fault reset. Automatic resets are possible only for
certain fault types and when the automatic reset function is
activated for that fault type.
3101 NR OF TRIALS Defines the number of automatic fault resets the drive
performs within the time defined by parameter
.
If the number of automatic resets exceeds the set number
(within the trial time), the drive prevents additional automatic
resets and remains stopped. The drive must be reset from
the control panel or from a source selected by parameter
Example:
Three faults have occurred during the trial time
. Last fault is reset only if the
is 3 or more.
0
0…5
Number of the automatic resets
1 = 1
3102 TRIAL TIME
Defines the time for the automatic fault reset function. See
.
30.0 s
1.0…600.0 s
Time
1 = 0.1 s
3103 DELAY TIME
Defines the time that the drive waits after a fault before
attempting an automatic reset. See parameter
. If delay time is set to zero, the drive resets
immediately.
0.0 s
0.0…120.0 s
Time
1 = 0.1 s
All parameters
No.
Name/Value
Description
Def/FbEq
X
X X
t
Trial time
X = Automatic reset