168 Actual signals and parameters
22 ACCEL/DECEL
Acceleration and deceleration times. See group
in the list of all parameters.
2202 ACCELER
TIME 1
Defines the acceleration time 1.
5.0 s
2203 DECELER
TIME 1
Defines the deceleration time 1.
5.0 s
53 EFB PROTOCOL
Embedded fieldbus link settings. See chapter
control with the embedded fieldbus
on page
.
5301 EFB
PROTOCOL ID
Contains the identification and program version of the
protocol.
Note:
You can reset this parameter only with parameter
-
5302 EFB STATION
ID
Defines the address of the device. Two units with the same
address are not allowed on-line.
1
5303 EFB BAUD
RATE
Defines the transfer rate of the link
9.6 kbit/s
5304 EFB PARITY
Defines the use of parity and stop bit(s) and the data length.
The same setting must be used in all on-line stations.
5305 EFB CTRL
PROFILE
Selects the communication profile. See section
.
5306 EFB OK
MESSAGES
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
0
5307 EFB CRC
MESSAGES
Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note:
High electromagnetic noise levels generate errors.
0
5308 EFB UART
ERRORS
Number of messages with a character error received by the
drive.
0
5309 EFB STATUS
Status of the EFB protocol.
5310 EFB PAR 10
Selects an actual value to be mapped to Modbus register
40005.
0
5311 EFB PAR 11
Selects an actual value to be mapped to Modbus register
40006.
0
5312 EFB PAR 12
Selects an actual value to be mapped to Modbus register
40007.
0
5313 EFB PAR 13
Selects an actual value to be mapped to Modbus register
40008.
0
5314 EFB PAR 14
Selects an actual value to be mapped to Modbus register
40009.
0
5315 EFB PAR 15
Selects an actual value to be mapped to Modbus register
40010.
0
5316 EFB PAR 16
Selects an actual value to be mapped to Modbus register
40011.
0
5317 EFB PAR 17
Selects an actual value to be mapped to Modbus register
40012.
0
5318 EFB PAR 18
For Modbus: Sets an additional delay before the drive
begins transmitting response to the master request.
0
Parameters in the short parameter view
No.
Name/Value
Description