Fieldbus control with the embedded fieldbus 287
13
Fieldbus control with the
embedded fieldbus
What this chapter contains
The chapter describes how the drive can be controlled by external devices over a
communication network using embedded fieldbus.
System overview
The drive is connected to an external control system through embedded fieldbus. The
embedded fieldbus supports Modbus RTU protocol. Modbus is a serial,
asynchronous protocol. Transaction is half-duplex.
The embedded fieldbus can be connected with either RS-232 (control panel
connector X2) or EIA-485 (I/O terminals 23…26). The maximum length of the
communication cable with RS-232 is restricted to 3 meters.
RS-232 is designed for a point-to-point application (a single master controlling one
slave). EIA-485 is designed for a multipoint application (a single master controlling
one or more slaves).
Note:
The RS-232 connection is supported from software version 4.02A onwards.