Actual signals and parameters 239
DI3U,4D(NC)
Digital input DI3: Reference increase. Digital input DI4:
Reference decrease. The program stores the active
reference (not reset by a stop command). The reference is
not saved if the control source is changed from EXT1 to
EXT2, from EXT2 to EXT1 or from LOC to REM.
12
AI1+AI2
Reference is calculated with the following equation:
REF = AI1(%) + AI2(%) - 50%
14
AI1*AI2
Reference is calculated with the following equation:
REF = AI(%) · (AI1(%) / 50%)
15
AI1-AI2
Reference is calculated with the following equation:
REF = AI1(%) + 50% - AI2(%)
16
AI1/AI2
Reference is calculated with the following equation:
REF = AI1(%) · (50% / AI2 (%))
17
INTERNAL
A constant value defined by parameter
,
. See also
19
DI4U,5D(NC)
See selection
.
31
FREQ INPUT
Frequency input
32
4011 INTERNAL
SETPNT
Selects a constant value as process PID controller
value is
set to
.
40
x…x
Unit and range depend on the unit and scale defined by
parameters
.
4012 SETPOINT
MIN
Defines the minimum value for the selected PID reference
.
0.0%
-500.0…500.0% Value in percent.
Example:
Analog input AI1 is selected as the PID reference
). The reference
minimum and maximum correspond to the
and
settings as follows:
1 = 0.1%
4013 SETPOINT
MAX
Defines the maximum value for the selected PID reference
signal source. See parameters
and
.
100.0%
-500.0…500.0% Value in percent
1 = 0.1%
4014 FBK SEL
Selects the process actual value (feedback signal) for the
process PID controller: The sources for the variables ACT1
and ACT2 are further defined by parameters
and
ACT1
ACT1
1
All parameters
No.
Name/Value
Description
Def/FbEq
(MAX)
(MIN)
AI1
(%)
Ref
Ref
AI1
(%)
(MIN)
(MAX)
MAX > MIN
MIN > MAX