Actual signals and parameters 187
13 ANALOG INPUTS
Analog input signal processing
1301 MINIMUM AI1
Defines the minimum %-value that corresponds to minimum
mA/(V) signal for analog input AI1. When used as a
reference, the value corresponds to the reference minimum
setting.
0…20 mA 0…100%
4…20 mA 20…100%
-10…10 mA -50…50%
Example:
If AI1 is selected as the source for external
reference REF1, this value corresponds to the value of
.
Note:
value must not exceed
value.
1.0%
-100.0…100.0% Value in percent of the full signal range.
Example:
If the minimum value for analog input is 4 mA, the
percent value for 0…20 mA range is:
(4 mA / 20 mA) · 100% = 20%
1 = 0.1%
1302 MAXIMUM AI1 Defines the maximum %-value that corresponds to
maximum mA/(V) signal for analog input AI1. When used as
a reference, the value corresponds to the reference
maximum setting.
0…20 mA 0…100%
4…20 mA 20…100%
-10…10 mA -50…50%
Example:
If AI1 is selected as the source for external
reference REF1, this value corresponds to the value of
.
100.0%
-100.0…100.0% Value in percent of the full signal range.
Example:
If the maximum value for analog input is 10 mA,
the percent value for 0…20 mA range is:
(10 mA / 20 mA) · 100% = 50%
1 = 0.1%
1303 FILTER AI1
Defines the filter time constant for analog input AI1, that is,
the time within which 63% of a step change is reached.
0.1 s
0.0…10.0 s
Filter time constant
1 = 0.1 s
1304 MINIMUM AI2
Defines the minimum %-value that corresponds to minimum
mA/(V) signal for analog input AI2. See parameter
1.0%
1 = 0.1%
1305 MAXIMUM AI2 Defines the maximum %-value that corresponds to
maximum mA/(V) signal for analog input AI2. See
.
100.0%
All parameters
No.
Name/Value
Description
Def/FbEq
=
=
=
=
=
=
Unfiltered signal
Filtered signal
Time constant
63
100
%
t