Actual signals and parameters 271
The table below shows the PFC motor assignments for
some typical settings in the relay output parameters
), where the settings are either = 31
), or = X (anything but 31), and where the Autochange
function is disabled (
= 0).
If five auxiliary motors are needed, use the transistor output
) as an additional relay output.
In relay order, TO is set between RO 1 and RO 2. The table
below shows the PFC motor assignments for some typical
settings when TO is in use.
The table below shows the PFC motor assignments for
some typical settings in the relay output parameters
), where the settings are either = 31
), or = X (anything but 31), and where the Autochange
function is enabled (
> 0).
All parameters
No.
Name/Value
Description
Def/FbEq
Parameter setting
Relay assignment
1
4
0
1
1
4
0
2
1
4
0
3
1
4
1
0
8
1
1
7
Autochange disabled
RO 1 RO 2 RO 3
RO 4
31 X X X 1
Aux. X
X
X
31 31 X X 2
Aux. Aux. X
X
31 31 31 X 3
Aux. Aux. Aux. X
X 31 31 X 2
X Aux. Aux. X
31
31
X
X
1*
Aux.
Aux.
X
X
* = One additional relay output for the PFC that is in use.
One motor is in “sleep” when the other is rotating.
Parameter setting
Relay assignment
1
4
0
1
1
8
0
5
1
4
0
2
1
4
0
3
1
4
1
0
8
1
1
7
Autochange disabled
RO 1 TO RO 2 RO 3 RO 4
31
X
X X X 1 Aux. X X X X
31 31
X
X X 2 Aux.
Aux. X. X X
31 31 31
X X 3 Aux.
Aux. Aux. X
X
31 31 31 31
X 4 Aux.
Aux. Aux.
Aux. X
31 31 31 31 31
5 Aux. Aux. Aux. Aux. Aux.
31 31 31 31
X
4* Aux. Aux. Aux. Aux. X
* = One additional relay output for the PFC that is in use.
One motor is in “sleep” when the other is rotating.
Parameter setting
Relay assignment
1
4
0
1
1
4
0
2
1
4
0
3
1
4
1
0
8
1
1
7
Autochange enabled
RO 1 RO 2 RO 3
RO 4
31 31 X X 1
PFC
PFC
X
X
31 31 31 X 2
PFC
PFC
PFC
X
X
31 31 X 1
X PFC
PFC
X
31
31
X
X
0**
PFC
PFC
X
X
** = No auxiliary motors, but the Autochange function is in
use. Working as a standard PID-control.