198 Actual signals and parameters
0.0…10.0 s
Filter time constant
1 = 0.1 s
1804 TO MODE
Selects the operation mode for the transistor output TO.
See section
on page
.
DIGITAL
Transistor output is used as a digital output DO.
0
FREQUENCY
Transistor output is used as a frequency output FO.
1
1805 DO SIGNAL
Selects a drive status indicated through digital output DO.
1806 DO ON DELAY Defines the operation delay for digital output DO.
0.0 s
0.0…3600.0 s
Delay time
1 = 0.1 s
1807 DO OFF
DELAY
Defines the release delay for digital output DO.
0.0 s
0.0…3600.0 s
Delay time
1 = 0.1 s
1808 FO CONTENT
SEL
Selects a drive signal to be connected to frequency output
FO.
104
x…x
Parameter index in group
. Eg 102 =
.
1809 FO CONTENT
MIN
Defines the minimum frequency output FO signal value.
Signal is selected with parameter
.
FO minimum and maximum correspond to
and
settings as follows:
-
x…x
Setting range depends on parameter
setting.
-
1810 FO CONTENT
MAX
Defines the maximum frequency output FO signal value.
Signal is selected with parameter
See parameter
.
-
x…x
Setting range depends on parameter
setting.
-
1811 MINIMUM FO
Defines the minimum value for frequency output FO.
10 Hz
10…16000 Hz
Minimum frequency. See parameter
1 = 1 Hz
1812 MAXIMUM FO Defines the maximum value for frequency output FO.
1000 Hz
10…16000 Hz
Maximum frequency. See parameter
1 = 1 Hz
1813 FILTER FO
Defines the filter time constant for frequency output FO, ie
the time within which 63% of a step change is reached.
0.1 s
0.0…10.0 s
Filter time constant
1 = 0.1 s