10 START/STOP/DIR
The sources for external start, stop and direction control
1001 EXT1
COMMANDS
Defines the connections and the source for the start, stop
and direction commands for external control location 1
(EXT1).
NOT SEL
No start, stop and direction command source
0
DI1
Start and stop through digital input DI1. 0 = stop, 1 = start.
Direction is fixed according to parameter
(setting
=
1
DI1,2
Start and stop through digital input DI1. 0 = stop, 1 = start.
Direction through digital input DI2. 0 = forward, 1 = reverse.
To control direction, parameter
setting
must be
.
2
DI1P,2P
Pulse start through digital input DI1. 0 -> 1: Start. (In order to
start the drive, digital input DI2 must be activated prior to the
pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction
of rotation is fixed according to parameter
(setting
=
Note:
When the stop input (DI2) is deactivated (no input),
the control panel start and stop keys are disabled.
3
DI1P,2P,3
Pulse start through digital input DI1. 0 -> 1: Start. (In order to
start the drive, digital input DI2 must be activated prior to the
pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction
through digital input DI3. 0 = forward, 1 = reverse. To control
setting must be
.
Note:
When the stop input (DI2) is deactivated (no input),
the control panel start and stop keys are disabled.
4
DI1P,2P,3P
Pulse start forward through digital input DI1. 0 -> 1: Start
forward. Pulse start reverse through digital input DI2. 0 -> 1:
Start reverse. (In order to start the drive, digital input DI3
must be activated prior to the pulse fed to DI1/DI2). Pulse
stop through digital input DI3. 1 -> 0: Stop. To control the
setting must be
.
Note:
When the stop input (DI3) is deactivated (no input),
the control panel start and stop keys are disabled.
5
KEYPAD
Start, stop and direction commands through control panel
when EXT1 is active. To control the direction, parameter
setting must be
8
DI1F,2R
Start, stop and direction commands through digital inputs
DI1 and DI2.
setting must be
3 (
).
9
DI1
DI2 Operation
0
0
Stop
1
0
Start forward
0
1
Start reverse
1
1
Stop