266 Actual signals and parameters
0.0…100.0%
Value in percent
1 = 0.1%
8105 REFERENCE
STEP 3
Sets a percentage value that is added to the process
reference. Applies only when at least three auxiliary
(constant speed) motors are running.
See parameter
0.0%
0.0…100.0%
Value in percent
1 = 0.1%
8109 START FREQ
1
Sets the frequency limit used to start the first auxiliary motor.
The first auxiliary motor starts if:
• no auxiliary motors are running
• drive output frequency exceeds limit
+ 1 Hz
• output frequency stays above a relaxed limit (
- 1 Hz)
for at least time
After the first auxiliary motor starts, output frequency
decreases by value (
In effect, the output of the speed regulated motor drops to
compensate for the input from the auxiliary motor.
E: 50.0 Hz
U: 60.0 Hz
See the figure, where:
A = (
B = Output frequency increase during the start delay.
C = Diagram showing auxiliary motor’s run status as
frequency increases (1 = On).
Note:
value must be between
) -1.
0.0…500.0 Hz
Frequency
1 = 0.1 Hz
8110 START FREQ
2
Sets the frequency limit used to start the second auxiliary
motor. See
for a complete description
of the operation.
The second auxiliary motor starts if:
• one auxiliary motor is running
• drive output frequency exceeds limit
+ 1 Hz
• output frequency stays above the relaxed limit (
-
1 Hz) for at least time
E: 50.0 Hz
U: 60.0 Hz
0.0…500.0 Hz
Frequency
1 = 0.1 Hz
All parameters
No.
Name/Value
Description
Def/FbEq
A
B
1
0
C
A
t
t
(
)+1
f
(Hz)
f
MAX
f
MIN