268 Actual signals and parameters
8113 LOW FREQ 2
Sets the frequency limit used to stop the second auxiliary
motor. See
for a complete description of
the operation.
The second auxiliary motor stops if:
• two auxiliary motors are running
• drive output frequency drops below limit
- 1 Hz
• output frequency stays below the relaxed limit (
+
1 Hz) for at least time
E: 25.0 Hz
U: 30.0 Hz
0.0…500.0 Hz
Frequency
1 = 0.1 Hz
8114 LOW FREQ 3
Sets the frequency limit used to stop the third auxiliary
motor. See
for a complete description of
the operation.
The third auxiliary motor stops if:
• three auxiliary motors are running
• drive output frequency drops below limit
- 1 Hz
• output frequency stays below the relaxed limit (
+
1 Hz) for at least time
E: 25.0 Hz
U: 30.0 Hz
0.0…500.0 Hz
Frequency
1 = 0.1 Hz
8115 AUX MOT
START D
Sets the start delay for the auxiliary motors.
The output frequency must remain above the start
frequency limit (parameter
,
) for this time
period before the auxiliary motor starts.
See
for a complete description of the
operation.
5.0 s
0.0…3600.0 s
Delay time
1 = 0.1 s
8116 AUX MOT
STOP D
Sets the stop delay for the auxiliary motors.
The output frequency must remain below the low frequency
limit (parameter
) for this time period
before the auxiliary motor stops.
See
for a complete description of the
operation.
3.0 s
0.0…3600.0 s
Delay time
1 = 0.1 s
All parameters
No.
Name/Value
Description
Def/FbEq