194 Actual signals and parameters
COMM
Fieldbus interface as the source for the fault reset signal, ie
Control word
bit 4 (with ABB drives
profile
bit 7). The Control word is sent by
the fieldbus controller through the embedded fieldbus
(Modbus) to the drive. For the Control word bits, see
on page
.
8
DI1(INV)
Reset through inverted digital input DI1 (reset on the falling
edge of DI1) or from the control panel
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
1605 USER PAR
SET CHG
Enables the change of the User parameter set through a
digital input. See parameter
. The
change is only allowed when the drive is stopped. During
the change, the drive does not start.
Note:
Always save the User parameter set with parameter
after changing any parameter setting, or reperforming
the motor identification. The last settings saved by the user
are loaded into use whenever the power is switched off and
on again or the parameter
setting is changed. Any
unsaved changes are lost.
Note:
The value of this parameter is not included in the
User parameter sets. A setting once made remains despite
User parameter set change.
Note:
Selection of User parameter set 2 can be supervised
through relay outputs RO 1…4 and digital output DO. See
parameters
…
,
and
NOT SEL
User parameter set change is not possible through a digital
input. Parameter sets can be changed only from the control
panel.
0
DI1
User parameter set control through digital input DI1. Falling
edge of digital input DI1: User parameter set 1 is loaded into
use. Rising edge of digital input DI1: User parameter set 2 is
loaded into use.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
DI1(INV)
User parameter set control through inverted digital input
DI1. Falling edge of inverted digital input DI1: User
parameter set 2 is loaded into use. Rising edge of inverted
digital input DI1: User parameter set 1 is loaded into use.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
All parameters
No.
Name/Value
Description
Def/FbEq