Technical data 345
Losses, cooling data and noise
Losses and cooling data
Frame size R0 has natural convection cooling. Frame sizes R1…R4 are provided
with an internal fan. The air flow direction is from bottom to top.
The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O and panel not in use) and maximum load
(all digital inputs in the on state and the panel, fieldbus and fan in use). The total heat
dissipation is the sum of the heat dissipation in the main and control circuits.
Type
Heat dissipation
Air flow
ACS310-
Main circuit
Control circuit
x = E/U
1)
Rated
I
LD
Min
Max
W
BTU/Hr
W
BTU/Hr
W
BTU/Hr
m
3
/h
ft
3
/min
1-phase
U
N
= 200…240 V
(200, 208, 220, 230, 240 V)
01x-02A4-2
19
65
6.1
21
22.7
78
-
-
01x-04A7-2
38
130
9.5
32
26.4
90
24
14
01x-06A7-2
60
205
9.5
32
26.4
90
24
14
01x-07A5-2
62
212
11
36
27.5
94
21
12
01x-09A8-2
83
283
11
36
27.5
94
21
12
3-phase
U
N
= 200…240 V
(200, 208, 220, 230, 240 V
03x-02A6-2
19
65
6.1
21
23
78
-
-
03x-03A9-2
31
106
6.1
21
23
78
-
-
03x-05A2-2
38
130
9.5
32
26
90
24
14
03x-07A4-2
60
205
9.5
32
26
90
24
14
03x-08A3-2
62
212
9.5
32
26
90
21
12
03x-10A8-2
83
283
11
36
28
94
21
12
03x-14A6-2
112
383
11
36
28
94
52
31
03x-19A4-2
152
519
11
36
28
94
52
31
03x-26A8-2
250
854
17
57
35
120
71
42
03x-34A1-2
270
922
33
110
58
200
96
57
03x-50A8-2
430
1469
33
110
58
200
96
57
3-phase
U
N
= 380…480 V
(380, 400, 415, 440, 460, 480 V)
03x-01A3-4
11
38
6.6
23
24
83
-
-
03x-02A1-4
16
55
6.6
23
24
83
-
-
03x-02A6-4
21
72
9.8
33
29
98
13
8
03x-03A6-4
31
106
9.8
33
29
98
13
8
03x-04A5-4
40
137
9.8
33
29
98
13
8
03x-06A2-4
61
208
9.8
33
29
98
19
11
03x-08A0-4
74
253
14
48
33
110
24
14
03x-09A7-4
94
321
14
48
33
110
24
14