Actual signals and parameters 209
2604 IR COMP
FREQ
Defines the frequency at which the IR compensation is 0 V.
See the figure for parameter
Note:
is set to
, this parameter is not active. The IR
compensation frequency is set by parameter
.
80%
0…100%
Value in percent of the motor frequency
1 = 1%
2605 U/F RATIO
Selects the voltage to frequency (U/f) ratio below the field
weakening point.
LINEAR
Linear ratio for constant torque applications.
1
SQUARED
Squared ratio for centrifugal pump and fan applications.
With squared U/f ratio the noise level is lower for most
operating frequencies.
2
USER
DEFINED
Custom ratio defined by parameters
. See
section
on page
3
2606 SWITCHING
FREQ
Defines the switching frequency of the drive. Higher
switching frequency results in lower acoustic noise. See
also parameter
and section
Switching frequency derating, I2N and ILD (= all currents)
on page
In multimotor systems, do not change the switching
frequency from the default value.
4 kHz
4 kHz
1 = 1 kHz
8 kHz
12 kHz
16 kHz
2607 SWITCH FREQ
CTRL
Activates the switching frequency control. When active, the
selection of parameter
is limited
when the drive internal temperature increases. See the
figure below. This function allows the highest possible
switching frequency at a specific operation point.
Higher switching frequency results in lower acoustic noise,
but higher internal losses.
ON
Active
1
All parameters
No.
Name/Value
Description
Def/FbEq
* Temperature depends on the drive output frequency.
16 kHz
4 kHz
Drive
temperature
f
sw
limit
80…100 °C *
100…120 °C *
T