Actual signals and parameters 207
DI1
Digital input DI1. 1 = ramp input is forced to zero. Ramp
output ramps to zero according to the used ramp time.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
COMM
Fieldbus interface as the source for forcing ramp input to
zero, ie Control word
bit 13 (with
ABB drives profile
bit 6). The Control
word is sent by the fieldbus controller through the
embedded fieldbus (Modbus) to the drive. For the Control
on page
and
ABB drives communication profile
on page
7
DI1(INV)
Inverted digital input DI1. 0 = ramp input is forced to zero.
Ramp output ramps to zero according to the used ramp
time.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
25 CRITICAL
SPEEDS
Speed (output frequency) bands within which the drive is not
allowed to operate.
2501 CRIT SPEED
SEL
Activates/deactivates the critical speeds function. The
critical speed function avoids specific output frequency
ranges.
Example:
A fan has vibrations in the range of 18 to 23 Hz
and 46 to 52 Hz. To make the drive to jump over the
vibration frequency ranges:
• Activate the critical speeds function.
• Set the critical frequency ranges as in the figure below.
OFF
Inactive
0
ON
Active
1
2502 CRIT SPEED 1
LO
Defines the minimum limit for critical output frequency range
1
0.0 Hz
0.0…500.0 Hz
Limit in Hz. The value cannot be above the maximum
(parameter
).
1 = 0.1 Hz
All parameters
No.
Name/Value
Description
Def/FbEq
18
23
46
52
1
= 18 Hz
2
= 23 Hz
3
= 46 Hz
4
= 52 Hz
1 2 3 4
f
output
(Hz)
f
reference
(Hz)