212 Actual signals and parameters
2906 RUN TIME
ACT
Defines the actual value for the drive run time counter.
has been set to a
non zero value, the counter starts. When the actual value of
the counter exceeds the value defined by parameter
, a
maintenance notice is displayed on the panel.
0.0 kh
0.0…6553.5 kh Time. Parameter is reset by setting it to zero.
1 = 0.1 kh
2907 USER MWh
TRIG
Defines the trigger point for the drive power consumption
counter. Value is compared to parameter
value.
0.0 MWh
0.0…6553.5
MWh
Megawatt hours. If parameter value is set to zero, the trigger
is disabled.
1 =
0.1 MWh
2908 USER MWh
ACT
Defines the actual value of the drive power consumption
has been
set to a non zero value, the counter starts. When the actual
value of the counter exceeds the value defined by
, a maintenance notice is displayed on the
panel.
0.0 MWh
0.0…6553.5
MWh
Megawatt hours. Parameter is reset by setting it to zero.
1 =
0.1 MWh
30 FAULT
FUNCTIONS
Programmable protection functions
3001 AI<MIN
FUNCTION
Defines the drive response if the analog input (AI) signal
drops below the fault limits and AI is used
• as the active reference source (group
)
• as the process or external PID controllers' feedback or
setpoint source (group
,
) and the
corresponding PID controller is active.
and
set the
fault limits.
NOT SEL
Protection is inactive.
0
FAULT
The drive trips on fault
coasts to stop. Fault limit is defined by parameter
.
1
CONST SP 7
The drive generates alarm
and sets
the speed to the value defined by parameter
. Alarm limit is defined by parameter
.
WARNING!
Make sure that it is safe to continue
operation in case the analog input signal is lost.
2
LAST SPEED
The drive generates alarm
and
freezes the speed to the level the drive was operating at.
The speed is determined considering the average speed
and time. Alarm limit is defined by parameter
.
WARNING!
Make sure that it is safe to continue
operation in case the analog input signal is lost.
3
All parameters
No.
Name/Value
Description
Def/FbEq