Actual signals and parameters 217
0.5…50.0 Hz
Frequency
1 = 0.1 Hz
3012 STALL TIME
Defines the time for the stall function. See parameter
.
20 s
10…400 s
Time
1 = 1 s
3016 SUPPLY
PHASE
Selects how the drive reacts to supply phase loss, ie when
DC voltage ripple is excessive.
FAULT
The drive trips on fault
and the motor
coasts to stop when the DC voltage ripple exceeds 14% of
the nominal DC voltage.
0
LIMIT/ALARM
Drive output current is limited and alarm
is generated when the DC voltage ripple exceeds
14% of the nominal DC voltage.
There is a 10 s delay between the activation of the alarm
and the output current limitation. The current is limited until
the DC voltage ripple drops under the ripple limit.
1
ALARM
The drive generates alarm
when the
DC ripple exceeds 14% of the nominal DC voltage.
2
3017 EARTH FAULT Selects how the drive reacts when an earth (ground) fault is
detected in the motor or the motor cable.
Note:
Disabling earth (ground) fault may void the warranty.
DISABLE
No action
0
ENABLE
The drive trips on fault
.
1
3018 COMM FAULT
FUNC
Selects how the drive reacts in a fieldbus communication
break. The time delay is defined by parameter
NOT SEL
Protection is inactive.
0
FAULT
Protection is active. The drive trips on fault
and coasts to stop.
1
CONST SP 7
Protection is active. The drive generates alarm
and sets the speed to the value defined by parameter
.
WARNING
! Make sure that it is safe to continue
operation in case of a communication break.
2
LAST SPEED
Protection is active. The drive generates alarm
and freezes the speed to the level the drive was operating
at. The speed is determined considering the average speed
and time.
WARNING
! Make sure that it is safe to continue
operation in case of a communication break.
3
3019 COMM FAULT
TIME
Defines the time delay for the fieldbus communication break
supervision. See parameter
.
3.0 s
0.0…600.0 s
Delay time
1 = 0.1 s
3021 AI1 FAULT
LIMIT
Defines a fault level for analog input AI1. If parameter
, the drive trips on fault
when the analog input signal falls below the set
level.
Do not set this limit below the level defined by parameter
.
0.0%
0.0…100.0%
Value in percent of the full signal range
1 = 0.1%