Actual signals and parameters 185
DI2,3(INV)
See selection
-8
DI3,4(INV)
See selection
-9
DI4,5(INV)
See selection
-10
DI1,2,3(INV)
Constant speed selection through inverted digital inputs DI1,
DI2 and DI3. 1 = DI active, 0 = DI inactive.
-12
DI3,4,5(INV)
See selection
-13
1202 CONST
SPEED 1
Defines constant speed (drive output frequency) 1.
E: 5.0 Hz
U: 6.0 Hz
0.0…500.0 Hz
Output frequency in Hz
1 = 0.1 Hz
1203 CONST
SPEED 2
Defines constant speed (drive output frequency) 2.
E: 10.0 Hz
U: 12.0 Hz
0.0…500.0 Hz
Output frequency in Hz
1 = 0.1 Hz
1204 CONST
SPEED 3
Defines constant speed (drive output frequency) 3.
E: 15.0 Hz
U: 18.0 Hz
0.0…500.0 Hz
Output frequency in Hz
1 = 0.1 Hz
1205 CONST
SPEED 4
Defines constant speed (drive output frequency) 4.
E: 20.0 Hz
U: 24.0 Hz
0.0…500.0 Hz
Output frequency in Hz
1 = 0.1 Hz
1206 CONST
SPEED 5
Defines constant speed (drive output frequency) 5.
E: 25.0 Hz
U: 30.0 Hz
0.0…500.0 Hz
Output frequency in Hz
1 = 0.1 Hz
1207 CONST
SPEED 6
Defines constant speed (drive output frequency) 6.
E: 40.0 Hz
U: 48.0 Hz
0.0…500.0 Hz
Output frequency in Hz
1 = 0.1 Hz
1208 CONST
SPEED 7
Defines constant speed (drive output frequency) 7.
Constant speed 7 is also used with fault functions (
and
E: 50.0 Hz
U: 60.0 Hz
0.0…500.0 Hz
Output frequency in Hz
1 = 0.1 Hz
All parameters
No.
Name/Value
Description
Def/FbEq
DI DI2 DI3 Operation
1
1
1 No constant speed
0
1
1 Speed defined by par.
1
0
1 Speed defined by par.
0
0
1 Speed defined by par.
1
1
0 Speed defined by par.
0
1
0 Speed defined by par.
1
0
0 Speed defined by par.
0
0
0 Speed defined by par.