4025 WAKE-UP DEV Defines the wake-up deviation for the sleep function. The
drive wakes up if the process actual value deviation from
the PID reference value exceeds the set wake-up deviation
) longer than the wake-up delay (
). Wake-up level
settings.
is set to 0:
Wake-up level = PID reference (
) - Wake-up deviation
).
is set to 1:
Wake-up level = PID reference (
) + Wake-up deviation
)
See also figures for parameter
0
x…x
Unit and range depend on the unit and scale defined by
parameters
.
4026 WAKE-UP
DELAY
Defines the wake-up delay for the sleep function. See
.
0.50 s
0.00…60.00 s
Wake-up delay
1 = 0.01 s
4027 PID 1 PARAM
SET
Defines the source from which the drive reads the signal
that selects between PID parameter set 1 and 2.
PID parameter set 1 is defined by parameters
.
PID parameter set 2 is defined by parameters
.
SET 1
PID SET 1 is active.
0
DI1
Digital input DI1. 1 = PID SET 2, 0 = PID SET 1.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
SET 2
PID SET 2 is active.
7
TIMED FUNC 1 Timed PID SET 1/2 control. Timed function 1 inactive = PID
SET 1, timed function 1 active = PID SET 2. See parameter
group
.
8
TIMED FUNC 2 See selection
.
9
TIMED FUNC 3 See selection
.
10
TIMED FUNC 4 See selection
.
11
DI1(INV)
Inverted digital input DI1. 0 = PID SET 2, 1 = PID SET 1.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5