4023 PID SLEEP
LEVEL
Defines the start limit for the sleep function. If the motor
speed is below a set level (
) longer than the sleep
delay (
), the drive shifts to the sleeping mode: The
motor is stopped and the control panel shows alarm
message
must be set to
.
0.0 Hz
0.0…500.0 Hz
Sleep start level
1 = 0.1 Hz
4024 PID SLEEP
DELAY
Defines the delay for the sleep start function. See parameter
. When the motor speed falls below
the sleep level, the counter starts. When the motor speed
exceeds the sleep level, the counter is reset.
60.0 s
0.0…3600.0 s
Sleep start delay
1 = 0.1 s
All parameters
No.
Name/Value
Description
Def/FbEq
Wake-up level
deviation (
t
<
t
sd
Output
frequency
Selected process actual
value
Stop
t
sd
= Sleep delay
)
Sleep level
(
Start
Wake-up delay
(
t
sd
Reference
t
Sleep boost step
(
Control
panel:
Sleep boost time (
)
t
t