89
Actual signals and parameters
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
0 = NOT SEL
Not selected
-1 = DI1(INV)
Inverted digital input DI1. 1 = jogging inactive, 0 = jogging active.
-2 = DI2(INV)
See selection DI1(INV).
-3 = DI3(INV)
See selection DI1(INV).
-4 = DI4(INV)
See selection DI1(INV).
-5 = DI5(INV)
See selection DI1(INV).
11 REFERENCE
SELECT
Panel reference type, local reference source, external control location
selection and external reference sources and limits
The drive can accept a variety of references in addition to the conventional
analog input, potentiometer and control panel signals:
- The drive reference can be given with two digital inputs: One digital input
increases the speed, the other decreases it.
- The drive can form a reference out of analog input and potentiometer
signals by using mathematical functions: Addition, subtraction.
- The drive reference can be given with a frequency input.
It is possible to scale the external reference so that the signal minimum and
maximum values correspond to a speed other than the minimum and
maximum speed limits.
1101
KEYPAD REF SEL
Selects the type of the reference in the local control mode.
1 = REF1
1 = REF1(Hz)
Frequency reference
2 = REF2(%)
%-reference
1102
EXT1/EXT2 SEL
Defines the source from which the drive reads the signal that selects
between two external control locations, EXT1 or EXT2.
0 = EXT1
0 = EXT1
EXT1 active. The control signal sources are defined by parameters
1001
EXT1 COMMANDS and
1103
REF1 SELECT.
1 = DI1
Digital input DI1. 0 = EXT1, 1 = EXT2.
2 = DI2
See selection DI1.
3 = DI3
See selection DI1.
4 = DI4
See selection DI1.
5 = DI5
See selection DI1.
7 = EXT2
EXT2 active. The control signal sources are defined by parameters
1002
EXT2 COMMANDS and
1106
REF2 SELECT.
-1 = DI1(INV)
Inverted digital input DI1. 1 = EXT1, 0 = EXT2.
-2 = DI2(INV)
See selection DI1(INV).
-3 = DI3(INV)
See selection DI1(INV).
-4 = DI4(INV)
See selection DI1(INV).
-5 = DI5(INV)
See selection DI1(INV).
1103
REF1 SELECT
Selects the signal source for external reference REF1.
1 = AI1
0 = KEYPAD
Control panel
1 = AI1
Analog input AI1
2 = POT
Potentiometer
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...