Actual signals and parameters
115
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
0,
x…x
Parameter index in group
01 OPERATING DATA
. For example, 102 =
0102
SPEED.
0 = not selected.
3202
SUPERV 1 LIM LO
Defines the low limit for the first supervised signal selected by parameter
3201
SUPERV 1 PARAM. Supervision wakes up if the value is below the
limit.
-
x…x
Setting range depends on parameter
3201
SUPERV 1 PARAM setting.
-
3203
SUPERV 1 LIM HI
Defines the high limit for the first supervised signal selected by parameter
3201
SUPERV 1 PARAM. Supervision wakes up if the value is above the
limit.
-
x…x
Setting range depends on parameter
3201
SUPERV 1 PARAM setting.
-
3204
SUPERV 2 PARAM
Selects the second supervised signal. Supervision limits are defined by
parameters
3205
SUPERV 2 LIM LO and
3206
SUPERV 2 LIM HI. See
parameter
3201
SUPERV 1 PARAM.
104
x…x
Parameter index in group
01 OPERATING DATA
. For example, 102 =
0102
SPEED.
3205
SUPERV 2 LIM LO
Defines the low limit for the second supervised signal selected by parameter
3204
SUPERV 2 PARAM. Supervision wakes up if the value is below the
limit.
-
x…x
Setting range depends on parameter
3204
SUPERV 2 PARAM setting.
-
3206
SUPERV 2 LIM HI
Defines the high limit for the second supervised signal selected by parameter
3204
SUPERV 2 PARAM. Supervision wakes up if the value is above the
limit.
-
x…x
Setting range depends on parameter
3204
SUPERV 2 PARAM setting.
-
3207
SUPERV 3 PARAM
Selects the third supervised signal. Supervision limits are defined by
parameters
3208
SUPERV 3 LIM LO and
3209
SUPERV 3 LIM HI. See
parameter
3201
SUPERV 1 PARAM.
105
x…x
Parameter index in group
01 OPERATING DATA
. For example, 102 =
0102
SPEED.
3208
SUPERV 3 LIM LO
Defines the low limit for the third supervised signal selected by parameter
3207
SUPERV 3 PARAM. Supervision wakes up if the value is below the
limit.
-
x…x
Setting range depends on parameter
3207
SUPERV 3 PARAM setting.
-
3209
SUPERV 3 LIM HI
Defines the high limit for the third supervised signal selected by parameter
3207
SUPERV 3 PARAM. Supervision wakes up if the value is above the
limit.
-
x…x
Setting range depends on parameter
3207
SUPERV 3 PARAM setting.
-
33 INFORMATION
Firmware package version, test date etc.
3301
FIRMWARE
Displays the version of the firmware package.
0000
…FFFF (hex)
For example, 135B hex
3302
LOADING PACKAGE
Displays the version of the loading package.
Type
dependent
2001
…20FF hex
2021 hex = ACS150-0nE-
2022 hex = ACS150-0nU-
3303
TEST DATE
Displays the test date.
00.00
Date value in format YY.WW (year, week)
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...