92
Actual signals and parameters
DI1
DI2
DI3
Operation
0
0
0
No constant speed
1
0
0
Speed defined by parameter
1202
CONST SPEED 1
0
1
0
Speed defined by parameter
1203
CONST SPEED 2
1
1
0
Speed defined by parameter
1204
CONST SPEED 3
0
0
1
Speed defined by parameter
1205
CONST SPEED 4
1
0
1
Speed defined by parameter
1206
CONST SPEED 5
0
1
1
Speed defined by parameter
1207
CONST SPEED 6
1
1
1
Speed defined by parameter
1208
CONST SPEED 7
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
12 CONSTANT SPEEDS
Constant speed selection and values.
It is possible to define seven positive constant speeds. Constant speeds are
selected with digital inputs. Constant speed activation overrides the external
speed reference. Constant speed selections are ignored if drive is in the local
control mode.
1201
CONST SPEED SEL
Selects the constant speed activation signal.
9 = DI3,4
0 = NOT SEL
No constant speed in use
1 = DI1
Speed defined by parameter
1202
CONST SPEED 1 is activated through
digital input DI1. 1 = active, 0 = inactive.
2 = DI2
Speed defined by parameter
1202
CONST SPEED 1 is activated through
digital input DI2. 1 = active, 0 = inactive.
3 = DI3
Speed defined by parameter
1202
CONST SPEED 1 is activated through
digital input DI3. 1 = active, 0 = inactive.
4 = DI4
Speed defined by parameter
1202
CONST SPEED 1 is activated through
digital input DI4. 1 = active, 0 = inactive.
5 = DI5
Speed defined by parameter
1202
CONST SPEED 1 is activated through
digital input DI5. 1 = active, 0 = inactive.
7 = DI1,2
Constant speed selection through digital inputs DI1 and DI2.1 = DI active,
0 = DI inactive.
DI1
DI2
Operation
0
0
No constant speed
1
0
Speed defined by parameter
1202
CONST SPEED 1
0
1
Speed defined by parameter
1203
CONST SPEED 2
1
1
Speed defined by parameter
1204
CONST SPEED 3
8 = DI2,3
See selection DI1,2.
9 = DI3,4
See selection DI1,2.
10 = DI4,5
See selection DI1,2.
12 = DI1,2,3
Constant speed selection through digital inputs DI1, DI2 and DI3.
1 = DI active, 0 = DI inactive.
13 = DI3,4,5
See selection DI1,2,3.
-1 = DI1(INV)
Speed defined by parameter
1202
CONST SPEED 1 is activated through
inverted digital input DI1. 0 = active, 1 = inactive.
-2 = DI2(INV)
Speed defined by parameter
1202
CONST SPEED 1 is activated through
inverted digital input DI2. 0 = active, 1 = inactive.
-3 = DI3(INV)
Speed defined by parameter
1202
CONST SPEED 1 is activated through
inverted digital input DI3. 0 = active, 1 = inactive.
-4 = DI4(INV)
Speed defined by parameter
1202
CONST SPEED 1 is activated through
inverted digital input DI4. 0 = active, 1 = inactive.
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...