88
Actual signals and parameters
Phase
Jog
cmd
Start
cmd
Description
1-2
1
0
Drive accelerates to the jogging speed along the
acceleration ramp of the jogging function.
2-3
1
0
Drive runs at the jogging speed.
3-4
0
0
Drive decelerates to zero speed along the deceleration
ramp of the jogging function.
4-5
0
0
Drive is stopped.
5-6
1
0
Drive accelerates to the jogging speed along the
acceleration ramp of the jogging function.
6-7
1
0
Drive runs at the jogging speed.
7-8
x
1
Normal operation overrides the jogging. Drive
accelerates to the speed reference along the active
acceleration ramp.
8-9
x
1
Normal operation overrides the jogging. Drive follows
the speed reference.
9-10
0
0
Drive decelerates to zero speed along the active
deceleration ramp.
10-
0
0
Drive is stopped.
x = State can be either 1 or 0.
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
1010
JOGGING SEL
Defines the signal that activates the jogging function. The jogging function is
typically used to control a cyclical movement of a machine section. One push
button controls the drive through the whole cycle: When it is on, the drive
starts, accelerates to a preset speed at a preset rate. When it is off, the drive
decelerates to zero speed at a preset rate.
The figure below describes the operation of the drive. It also represent how
the drive shifts to normal operation (= jogging inactive) when the drive start
command is switched on. Jog cmd = state of the jogging input, Start cmd =
state of the drive start command.
Speed
t
1 2
3 4 5
6
7
8 9
10
Note:
The jogging is not operational when the drive start command is on.
Note:
The jogging speed overrides the constant speeds (
12 CONSTANT
SPEEDS
).
Note:
The ramp shape time (
2207
RAMP SHAPE 2) must be set to zero
during jogging (that is, linear ramp).
Jogging speed is defined by parameter
1208
CONST SPEED 7, acceleration
and deceleration times are defined by parameters
2205
ACCELER TIME 2
and
2206
DECERLER TIME 2. See also parameter
2112
ZERO SPEED
DELAY.
0 = NOT SEL
1 = DI1
Digital input DI1. 0 = jogging inactive, 1 = jogging active.
2 = DI2
See selection DI1.
3 = DI3
See selection DI1.
4 = DI4
See selection DI1.
5 = DI5
See selection DI1.
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...