Technical data
146
Control connection data
Analog input X1A: AI(1)
Voltage signal, unipolar
0 (2)…10 V,
R
in
> 312 kohm
Current signal, unipolar
0
(4)…20 mA,
R
in
= 100 ohm
Potentiometer reference value
(
X1A:
+10V)
10 V ± 1%, max. 10 mA,
R
< 10 kohm
Resolution
0.1%
Accuracy
±1%
Auxiliary voltage X1A: +24V
24 V DC ± 10%, max. 200 mA
Digital inputs X1A: DI1...DI5
(frequency input DI5)
Voltage
12
…24 V DC with internal or external supply
Max. voltage for digital inputs 30 V DC
Type
PNP and NPN
Input impedance
2.4 kohm
Frequency input X1A: DI5
DI5 can be used either as a digital or as a frequency input.
Frequency input
Pulse train 0
…16 kHz (DI5 only)
Relay output X1A:
COM, NC, NO
Type
NO + NC
Max. switching voltage
250 V AC / 30 V DC
Max. switching current
0.5 A / 30 V DC; 5 A / 230 V AC
Max. continuous current
2 A rms
Wire size
Relay connections
I/O connections
Torque
Relay connections
I/O connections
1.5...0.20 mm
2
/16...24 AWG
1... 0.14mm
2
/16...26 AWG
0.5 N·m / 4.4 lbf·in
0.22 N·m / 2 lbf·in
Brake resistor connection
Short-circuit protection
(IEC 61800-5-1, IEC 60439-1,
UL 508C)
The brake resistor output is conditionally short-circuit proof by IEC/EN 61800-5-1 and UL
508C. For correct fuse selection, contact your local ABB representative. Rated conditional
short-circuit current as defined in IEC 60439-1 and the short-circuit test current by UL
508C is 100 kA.
Efficiency
Approximately 95 to 98% at nominal power level, depending on the drive size and options
Degrees of protection
IP20 (cabinet installation) / UL open: Standard enclosure. The drive must be installed in a
cabinet to fulfil the requirements for shielding from contact.
IP20 / NEMA 1: Achieved with an option kit (MUL1-R1) including a hood and a connection
box.
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...