Actual signals and parameters
121
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
11 = DI3U,4D(RNC)
Digital input DI3: Reference increase. Digital input DI4: Reference decrease.
Stop command resets the reference to zero. When this selection becomes
active (in change from EXT1 to EXT2), the reference initializes to the value
used when this control location (and this selection) was active the last time.
12 = DI3U,4D(NC)
Digital input DI3: Reference increase. Digital input DI4: Reference decrease.
The program stores the active reference (not reset by a stop command).
When this selection becomes active (in change from EXT1 to EXT2), the
reference initializes to the value used when this control location (and this
selection) was active the last time.
14 = AI1+POT
Reference is calculated with the following equation:
REF = AI1(%) + POT(%) - 50%
15 = AI1*POT
Reference is calculated with the following equation:
REF = AI(%) · (POT(%) / 50%)
16 = AI1-POT
Reference is calculated with the following equation:
REF = AI1(%) + 50% - POT(%)
17 = AI1/POT
Reference is calculated with the following equation:
REF = AI1(%) · (50% / POT (%))
19 = INTERNAL
A constant value defined by parameter
4011
INTERNAL SETPNT
31 = DI4U,5D(NC)
See selection DI3U,4D(NC).
32 = FREQ INPUT
Frequency input
4011
INTERNAL SETPNT
Selects a constant value as process PID controller reference, when
parameter
4010
SET POINT SEL value is set to 19 (INTERNAL).
40
x…x
Unit and range depend on the unit and scale defined by parameters
4006
UNITS and
4007
UNIT SCALE.
4012
SETPOINT MIN
Defines the minimum value for the selected PID reference signal source. See
parameter
4010
SET POINT SEL.
0.0%
-500
.0…500.0%
Value in percent.
Example:
Analog input AI1 is selected as the PID reference source (value of
parameter
4010
SET POINT SEL is 1 = AI1). The reference minimum and
maximum correspond to the
1301
MINIMUM AI1 and
1302
MAXIMUM AI1
settings as follows:
Ref
MAX > MIN
4012
Ref
MIN > MAX
4013
(MIN)
(MAX)
4012
4013
(MIN)
AI1
(%)
(MAX)
AI1
(%)
1301
1302
1301
1302
4013
SETPOINT MAX
Defines the maximum value for the selected PID reference signal source.
See parameters
4010
SET POINT SEL and
4012
SETPOINT MIN.
100.0%
-500
.0…500.0%
Value in percent
4014
FBK SEL
Selects the process actual value (feedback signal) for the process PID
controller: The sources for the variables ACT1 and ACT2 are further defined
by parameters
4016
ACT1 INPUT and
4017
ACT2 INPUT.
1 = ACT1
1 = ACT1
ACT1
2 = ACT1-ACT2
Subtraction of ACT1 and ACT 2
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...