54
Start-up and control with I/O
To change the direction of the motor rotation:
• Disconnect input power from the drive, and wait 5 minutes
for the intermediate circuit capacitors to discharge. Measure
the voltage between each input terminal (U1, V1 and W1)
and earth with a multimeter to ensure that the drive is
discharged.
• Exchange the position of two motor cable phase conductors
at the drive output terminals or at the motor connection box.
• Verify your work by applying input power and repeating the
check as described above.
forward
direction
reverse
direction
ACCELERATION/DECELERATION TIMES
Set the acceleration time 1 (parameter
2202
ACCELER
TIME 1).
Note:
Set also acceleration time 2 (parameter
2205
) if two
acceleration times will be used in the application.
Set the deceleration time 1 (parameter
2203
DECELER
TIME 1).
Note:
Set also deceleration time 2 (parameter
2206
) if two
deceleration times will be used in the application.
LOC
2202
s
PAR
FWD
LOC
2203
s
PAR
FWD
FINAL CHECK
The start-up is now completed. Check that there are no faults
or alarms shown on the display.
The drive is now ready for use.
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...