84
Actual signals and parameters
Actual signals
The following table includes the descriptions of all actual signal.
Actual signals
No.
Name/Value
Description
01 OPERATING DATA
Basic signals for monitoring the drive (read-only).
For actual signal supervision, see parameter group
32 SUPERVISION
.
For selection of an actual signal to be displayed on the control panel, see parameter
group
34 PANEL DISPLAY
.
0101 SPEED & DIR
Calculated motor speed in rpm. A negative value indicates reverse direction.
0102 SPEED
Calculated motor speed in rpm.
0103 OUTPUT FREQ
Calculated drive output frequency in Hz. (Shown by default on the panel Output mode
display.)
0104 CURRENT
Measured motor current in A
0105 TORQUE
Calculated motor torque in percent of the motor nominal torque
0106 POWER
Measured motor power in kW
0107 DC BUS VOLTAGE
Measured intermediate circuit voltage in V DC
0109 OUTPUT VOLTAGE
Calculated motor voltage in V AC
0110 DRIVE TEMP
Measured IGBT temperature in °C
0111
EXTERNAL REF 1
External reference REF1 in Hz
0112 EXTERNAL REF 2
External reference REF2 in percent. 100% equals the maximum motor speed.
0113 CTRL LOCATION
Active control location. (0) LOCAL; (1) EXT1; (2) EXT2.
0114 RUN TIME (R)
Elapsed drive running time counter (hours). Runs when the drive is modulating. The
counter can be reset by pressing the UP and DOWN keys simultaneously when the
control panel is in the Parameter mode.
0115 KWH COUNTER (R)
kWh counter. The counter value is accumulated till it reaches 65535 after which the
counter rolls over and starts again from 0. The counter can be reset by pressing UP and
DOWN keys simultaneously when the control panel is in the Parameter mode.
0120 AI 1
Relative value of analog input AI1 in percent
0121 POT
Potentiometer value in percent
0126 PID 1 OUTPUT
Output value of the process PID1 controller in percent
0128 PID 1 SETPNT
Setpoint signal (reference) for the process PID1 controller. Unit depends on parameter
4006
UNITS and
4007
UNIT SCALE settings.
0130 PID 1 FBK
Feedback signal for the process PID1 controller. Unit depends on parameter
4006
UNITS
and
4007
UNIT SCALE settings.
0132 PID 1 DEVIATION
Deviation of the process PID1 controller, that is the difference between the reference
value and the actual value. Unit depends on parameter
4006
UNITS and
4007
UNIT
SCALE.
0137 PROCESS VAR 1
Process variable 1 defined by parameter group
34 PANEL DISPLAY
0138 PROCESS VAR 2
Process variable 2 defined by parameter group
34 PANEL DISPLAY
0139 PROCESS VAR 3
Process variable 3 defined by parameter group
34 PANEL DISPLAY
0140 RUN TIME
Elapsed drive running time counter (thousands of hours). Runs when the drive is
modulating. Counter cannot be reset.
0141 MWH COUNTER
MWh counter. The counter value is accumulated till it reaches 65535 after which the
counter rolls over and starts again from 0. Cannot be reset.
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...