Actual signals and parameters
103
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
2205
ACCELER TIME 2
Defines the acceleration time 2, that is the time required for the speed to
change from zero to the speed defined by parameter
2008
MAXIMUM FREQ.
See parameter
2202
ACCELER TIME 1.
Acceleration time 2 is used also as jogging acceleration time. See parameter
1010
JOGGING SEL.
60.0 s
0.0
…1800.0 s
Time
2206
DECELER TIME 2
Defines the deceleration time 2, that is the time required for the speed to
change from the value defined by parameter
2008
MAXIMUM FREQ to zero.
See parameter
2203
DECELER TIME 1.
Deceleration time 2 is used also as jogging deceleration time. See parameter
1010
JOGGING SEL.
60.0 s
0.0
…1800.0 s
Time
2207
RAMP SHAPE 2
Selects the shape of the acceleration/deceleration ramp 2. The function is
deactivated during emergency stop (
2109
EMERG STOP SEL).
Ramp shape 2 is used also as jogging ramp shape time. See parameter
1010
JOGGING SEL.
0.0 = LINEAR
0.0 = LINEAR
0.
0…1000.0 s
See parameter
2204
RAMP SHAPE 1.
2208
EMERG DEC TIME
Defines the time within which the drive is stopped if an emergency stop is
activated. See parameter
2109
EMERG STOP SEL.
1.0 s
0.0
…1800.0 s
Time
2209
RAMP INPUT 0
Defines the source for forcing the ramp input to zero.
0 = NOT SEL
0 = NOT SEL
Not selected
1 = DI1
Digital input DI1. 1 = ramp input is forced to zero. Ramp output ramps to zero
according to the used ramp time.
2 = DI2
See selection DI1.
3 = DI3
See selection DI1.
4 = DI4
See selection DI1.
5 = DI5
See selection DI1.
-1 = DI1(INV)
Inverted digital input DI1. 0 = ramp input is forced to zero. Ramp output
ramps to zero according to the used ramp time.
-2 = DI2(INV)
See selection DI1(INV).
-3 = DI3(INV)
See selection DI1(INV).
-4 = DI4(INV)
See selection DI1(INV).
-5 = DI5(INV)
See selection DI1(INV).
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...