Actual signals and parameters
125
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
2 = 3-WIRE
3-wire macro for constant speed applications
3 = ALTERNATE
Alternate macro for start forward and start reverse applications
4 = MOTOR POT
Motor potentiometer macro for digital signal speed control applications
5 = HAND/AUTO
Hand/Auto macro to be used when two control devices are connected to the
drive:
- Device 1 communicates through the interface defined by external control
location EXT1.
- Device 2 communicates through the interface defined by external control
location EXT2.
EXT1 or EXT2 is active at a time. Switching between EXT1/2 through digital
input.
6 = PID CONTROL
PID control. For applications in which the drive controls a process value. For
example, pressure control by the drive running the pressure boost pump.
Measured pressure and the pressure reference are connected to the drive.
31 = LOAD FD SET
FlashDrop parameter values as defined by the FlashDrop file. Parameter
view is selected by parameter
1611
PARAMETER VIEW.
FlashDrop is an optional device for fast copying of parameters to unpowered
drives. FlashDrop allows easy customisation of the parameter list, for
example, selected parameters can be hidden. For more information, see
MFDT-01 FlashDrop user
’s manual
(3AFE68591074 [English]).
0 = USER S1 LOAD
User 1 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
-1 = USER S1 SAVE
Save User 1 macro. Stores the current parameter settings and the motor
model.
-2 = USER S2 LOAD
User 2 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
-3 = USER S2 SAVE
Save User 2 macro. Stores the current parameter settings and the motor
model.
-4 = USER S3 LOAD
User 3 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
-5 = USER S3 SAVE
Save User 3 macro. Stores the current parameter settings and the motor
model.
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...