95
Actual signals and parameters
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
7 = STARTED
The drive has received a start command. Relay is energized even if Run
enable signal is off. Relay is de-energized when drive receives a stop
command or a fault occurs.
8 = SUPRV 1 OVER
Status according to supervision parameters
3201
SUPERV 1 PARAM,
3202
SUPERV 1 LIM LO and
3203
SUPERV 1 LIM HI.
9 = SUPRV 1 UNDER
See selection SUPRV 1 OVER.
10 = SUPRV 2 OVER
Status according to supervision parameters
3204
SUPERV 2 PARAM,
3205
SUPERV 2 LIM LO and
3206
SUPERV 2 LIM HI.
11 = SUPRV 2 UNDER
See selection SUPRV 2 OVER.
12 = SUPRV 3 OVER
Status according to supervision parameters
3207
SUPERV 3 PARAM,
3208
SUPERV 3 LIM LO and
3209
SUPERV 3 LIM HI.
13 = SUPRV 3
UNDER
See selection SUPRV 3 OVER.
14 = AT SET POINT
Output frequency is equal to the reference frequency.
15 = FAULT(RST)
Fault. Automatic reset after the autoreset delay. See parameter group
31 AUTOMATIC RESET
.
16 = FLT/ALARM
Fault or alarm
17 = EXT CTRL
Drive is under external control.
18 = REF 2 SEL
External reference REF2 is in use.
19 = CONST FREQ
A constant speed is in use. See parameter group
12 CONSTANT SPEEDS
.
20 = REF LOSS
Reference or active control location is lost.
21 = OVERCURRENT
Alarm/Fault by overcurrent protection function
22 = OVERVOLTAGE
Alarm/Fault by overvoltage protection function
23 = DRIVE TEMP
Alarm/Fault by drive overtemperature protection function
24 =UNDERVOLTAGE
Alarm/Fault by undervoltage protection function
25 = AI1 LOSS
Analog input AI1 signal is lost.
27 = MOTOR TEMP
Alarm/Fault by motor overtemperature protection function. See parameter
3005
MOT THERM PROT.
28 = STALL
Alarm/Fault by stall protection function. See parameter
3010
STALL
FUNCTION.
29 = UNDERLOAD
Alarm/Fault by underload protection function. See parameter
3013
UNDERLOAD FUNC.
30 = PID SLEEP
PID sleep function. See parameter group
40 PROCESS PID SET 1
.
33 = FLUX READY
Motor is magnetized and able to supply nominal torque.
1404
RO 1 ON DELAY
Defines the operation delay for relay output RO.
0.0 s
0.0
…3600.0 s
Delay time. The figure below illustrates the operation (on) and release (off)
delays for relay output RO.
Control event
Relay status
1404 On delay
1405 Off delay
1405
RO 1 OFF DELAY
Defines the release delay for relay output RO.
0.0 s
0.0
…3600.0 s
Delay time. See the figure for parameter
1404
RO 1 ON DELAY.
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...