Actual signals and parameters
100
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
2103
DC MAGN TIME
Defines the pre-magnetizing time. See parameter
2101
START FUNCTION.
After the start command, the drive automatically pre-magnetizes the motor
for the defined time.
0.30 s
0.00
…10.00 s
Magnetizing time. Set this value long enough to allow full motor
magnetization. Too long a time heats the motor excessively.
2104
DC HOLD CTL
Activates the DC braking function.
0 = NOT SEL
0 = NOT SEL
Inactive
2 = DC BRAKING
DC current braking function active.
If parameter
2102
STOP FUNCTION is set to 1(COAST), DC braking is
applied after the start command is removed.
If parameter
2102
STOP FUNCTION is set to 2 (RAMP), DC braking is
applied after the ramp.
2106
DC CURR REF
Defines the DC braking current. See parameter
2104
DC HOLD CTL.
30%
0
…100%
Value in percent of the motor nominal current (parameter
9906
MOTOR NOM
CURR)
2107
DC BRAKE TIME
Defines the DC braking time.
0.0 s
0.0
…250.0 s
Time
2108
START INHIBIT
Sets the Start inhibit function on or off. If the drive is not actively started and
running, the Start inhibit function ignores a pending start command in any of
the following situations and a new start command is required:
- a fault is reset.
- Run enable signal activates while the start command is active. See
parameter
1601
RUN ENABLE.
- the control mode changes from local to remote.
- the external control mode switches from EXT1 to EXT2 or from EXT2 to
EXT1.
0 = OFF
0 = OFF
Disabled
1 = ON
Enabled
2109
EMERG STOP SEL
Selects the source for the external emergency stop command.
The drive cannot be restarted before the emergency stop command is reset.
Note:
The installation must include emergency stop devices and any other
safety equipment that may be needed. Pressing the stop key on the drive
’s
control panel does NOT
- generate an emergency stop of the motor.
- separate the drive from dangerous potential.
0 = NOT SEL
0 = NOT SEL
Emergency stop function is not selected.
1 = DI1
Digital input DI1. 1 = stop along the emergency stop ramp. See parameter
2208
EMERG DEC TIME. 0 = emergency stop command reset.
2 = DI2
See selection DI1.
3 = DI3
See selection DI1.
4 = DI4
See selection DI1.
5 = DI5
See selection DI1.
-1 = DI1(INV)
Inverted digital input DI. 0 = stop along the emergency stop ramp. See
parameter
2208
EMERG DEC TIME. 1 = emergency stop command reset
-2 = DI2(INV)
See selection DI1(INV).
-3 = DI3(INV)
See selection DI1(INV).
Summary of Contents for ACS150 series
Page 4: ......
Page 5: ......
Page 15: ...14 Safety ...
Page 19: ...18 Introduction to the manual ...
Page 39: ...38 Planning the electrical installation ...
Page 51: ...50 Installation checklist ...
Page 57: ...56 Start up and control with I O ...
Page 69: ...68 Control panel ...
Page 79: ...78 Application macros ...
Page 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Page 161: ...ji 4 I 5 I 6 4 J ...
Page 162: ......
Page 163: ...160 Dimension drawings ...
Page 169: ...166 Appendix Process PID control ...
Page 171: ...168 ...