Two-way wireless system ABAX
ACU-100
48
12.2.12 ASW-100 E and ASW-100 F controllers
Use the
S
and
T
keys to select the operating mode of the ASW-100 controller.
13. R
ESTORING CONTROLLER DEFAULT SETTINGS
The following parameters are preprogrammed by default:
•
service code: 12345;
•
D
LOAD
10
identifier: 0000000000000000;
•
response period: 24s;
•
problem signaling: LED indicator;
•
no registered wireless devices.
The default (factory) settings can be restored by means of the
S
ET DEFAULT
function
in the
keypad connected to the controller, or by way of
hardware restart
. In order to restore the
defaults by means of the hardware restart, follow the instructions below:
1. Disconnect the controller power supply.
2. Disconnect the cables connected to the controller communication bus.
3. Short the CLK and DAT terminals.
4. Reconnect the power supply. A short while after power-up, the operating mode LED
indicator will light in red. When default settings are restored, the LED color will change to
green.
5. Open the CLK and DAT terminals.
6. Disconnect the controller power supply.
7. Reconnect the cables to the controller communication bus.
8. Reconnect the controller power supply.
14. S
PECIFICATIONS
Operating frequency band................................................................... 868.0 MHz ÷ 868.6 MHz
Number of supported wireless devices ..................................................................................48
Range ..............................................................................................up to 500 m (in open area)
Supply voltage ................................................................................................... 12 V DC ±15%
Standby current consumption ........................................................................................140 mA
Maximum current consumption ......................................................................................140 mA
Outputs current-carrying capacity ....................................................................................50 mA
Security grade according to EN50131-3 ....................................................................... Grade 2
Environmental class according to EN50130-5 .........................................................................II
Operating temperature range............................................................................ -10 °C…+55 °C
Maximum humidity ..........................................................................................................93±3%
Complied with standards. EN 50130-4, EN 50130-5, EN 50131-1, EN 50131-3, EN 50131-5-3
Electronics board dimensions ............................................................................... 104 x 73 mm
Housing dimensions, OPU-1 A ................................................................... 126 x 158 x 32 mm
Weight............................................................................................................................... 222 g
Name of certification body........................................................................................Telefication