Two-way wireless system ABAX
ACU-100
24
– requires 2 inputs and at least 1 controller output when used in conjunction with other
control panels (the output is assigned to each of the two positions occupied by the siren
on the list of devices, hence it is possible to assign two outputs, but the same information
will be supplied to both of them ).
Information on power supply status and tampers is conveyed by means of the alarm system
zones / controller outputs.
The siren allows for independent triggering of two different types of signaling with
programmable parameters.
A command to trigger the signaling is only send to the siren
during the response time.
Hence the cutoff time of the control panel outputs which control
the ASP-205 wireless indoor siren must be longer than the response time. It is recommended
that this time correspond to the signaling duration, as programmed in the siren.
Violation of the siren tamper contact will generate tamper alarm, which will last 3 minutes
(sound type 1 and optical signaling).
Depending on the controller operating configuration, the low battery will:
– cause violation of both zones occupied by the siren in the system (communication through
the bus with INTEGRA, VERSA, CA-64 or CA-10 control panels);
– activate the controller LBA output;
– activate the controller outputs assigned to both positions occupied by the siren on the list
of devices.
7.3 A
DDITIONAL SIREN PARAMETERS TO BE CONFIGURED
ASP-105
– wireless triggered outdoor siren. The following is to be programmed:
– type of acoustic signaling;
– maximum duration of acoustic signaling.
ASP-205
– wireless indoor siren. You can program two types of signaling, defining for each
of them:
– maximum duration of signaling;
– type of acoustic signaling;
– whether optical signaling is to be enabled.
8. ASW-100
230V
AC
WIRELESS CONTROLLERS IN
ABAX
SYSTEM
The 230 V AC wireless controller:
– takes up 1 position on the list of wireless devices supported by the ACU-100 controller;
– occupies 1 output and 1 zone in the INTEGRA or VERSA alarm system;
– takes up 1 zone and additionally requires 1 ACU-100 controller input to control operation
in the CA-64 or CA-10 alarm system;
– requires 1 zone and 1 ACU-100 controller output when working with other control panels.
Depending on the ASW-100 controller operating configuration, the electric circuit is closed:
– on activating the INTEGRA or VERSA system output to which the ASW-100 controller is
assigned. The output must be programmed accordingly.
– on activating the ACU-100 controller input which has been selected as the control one.
The command to close/open the 230 V electric circuit is transmitted by the ACU-100
controller to the ASW-100 controller at once.
The ASW-100 E and ASW-100 F controllers can work in three modes (given in square
brackets is mode description in the LCD keypad of INTEGRA or VERSA system):
−
mode 0 [button: inactive] – the electric circuit is only remotely controlled;