Two-way wireless system ABAX
ACU-100
30
When interacting with the CA-64 control panel, the ACU-100 controller makes 48 wireless
zones available to it. The zone numbers are assigned to the wireless devices registered in
the controller according to the following principle:
zone number = 16 + number of the wireless device on the list
The system zones to which wireless devices are assigned can be programmed as:
– NC, NO or EOL – depending on the type of device, the zone will provide information
about detector violation, power failure, etc.
– 2EOL/NC or 2EOL/NO – depending on the type of device, the zone will provide
information about detector violation, power failure, etc., and, additionally, about tampers.
Connection of the controller to the CA-64 alarm control panel excludes the possibility to
connect to it the zone expanders (CA-64 E, CA-64 EPS and CA-64 ADR) as well as the
CA-64 PP zones & outputs expander with power supply.
10.3 Z
ONE EXPANDER FOR
CA-10
CONTROL PANEL
Fig. 11. Example of setting the DIP-switches.
Using the DIP-switches, set the suitable operating mode, address and programming mode of
the ACU-100 controller. To determine the operating mode you should take into account the
number of keypads installed in the system. Depending on the number of keypads, the
controller makes it possible to expand the system by 2, 4 or 6 wireless zones (see Table 9),
the status of which (violations and tampers of the wireless devices assigned to these zones)
will be transmitted by means of the communication bus.
Numbers of additional system zones
(zones 9 and 10 are reserved in the system for the 1
st
keypad zones)
Nu
mb
er o
f keyp
ad
s in
th
e
syst
em
Conne
c
tion of
CLK
keyp
ad
ter
m
in
als to
c
ontrol pa
ne
l
te
rmina
ls
Conne
c
tion of
CLK
controller terminals to
c
ontrol pa
ne
l
te
rmina
ls
11 12 13 14 15 16
1 CLK1 CLK2
output 11
in controller
output 12
in controller
output 13
in controller
output 14
in controller
output 15
in controller
output 16
in controller
2
CLK1
CLK2
CLK3
zone in 2
nd
keypad
zone in 2
nd
keypad
output 13
in controller
output 14
in controller
output 15
in controller
output 16
in controller
3
CLK1
CLK2
CLK3
CLK4
zone in 2
nd
keypad
zone in 2
nd
keypad
zone in 3
rd
keypad
zone in 3
rd
keypad
output 15
in controller
output 16
in controller
Table 9.
Control of the detectors (changeover to active/passive state), sirens (triggering alarm signal),
230 V AC controller (closing/opening the electric circuit) etc. is performed through the control
inputs of the ACU-100 controller. Suitably programmed outputs of the alarm control panel
should be connected to the control inputs. Additionally, it is possible to connect the first eight
outputs of the controller to the control panel zones. Thus the alarm control panel can receive
programming:
D
LOAD
10
address:
0011
operating mode:
CA-10 control panel with 1 keypad