For example, entering the 0-2-4 means that the heat detector has been disabled, acoustic
signaling type 2 has been selected, and the signaling by means of buzzer/LEDs will last 9
minutes.
12.1.8 ARD-100
detector
Enter a digit from the 1 to 16 range, corresponding to the selected sensitivity (1 – minimum;
16 – maximum).
12.1.9 ATD-100
detector
For each position taken by the detector enter in turn:
– letter H (high temperature threshold) or L (low temperature threshold);
– numerical value corresponding to a temperature from the -30° C to +70° C range (with up
to 0.5° accuracy),
– numerical value corresponding to a tolerance from the 0.5° C to 10° C range (with up to
0.5° accuracy).
12.1.10 ASP-105 siren
Program the acoustic signaling parameters (the first position / the first zone to which the siren
is assigned), i.e. enter the two-digit sequence, according to Table 12.
1st digit
2nd digit
digit
acoustic signaling
digit
signaling duration
1
sound type 1
1
1 minute
2
sound type 2
2
3 minutes
3
sound type 3
3
6 minutes
4
sound type 4
4
9 minutes
Table 12.
For example, entering the values 2-3 means that acoustic signaling type 2 has been selected
and that its duration will be 6 minutes.
12.1.11 ASP-205 siren
Determine the signaling parameters independently for both positions / zones occupied by the
siren, entering in each case a 3-digit sequence, according to Table 13.
1st digit
2nd digit
3rd digit
digit
signaling duration
digit
acoustic signaling
digit
optical signaling
1 1
minute 0
none
0 disabled
2
3 minutes
1
sound type 1
1
enabled
3
6 minutes
2
sound type 2
-
-
4
9 minutes
3
sound type 3
-
-
Table 13.
For example, entering the values 2-0-1 means that the signaling will last 3 minutes, the
acoustic signaling has been disabled, and the optical signaling enabled.
12.1.12 ASW-100 E and ASW-100 F controllers
Enter a digit from the 0 to 2 range, which corresponds to the selected mode of operation.