Two-way wireless system ABAX
ACU-100
46
12.2 LCD
KEYPAD
In the LCD keypad of INTEGRA system, additional parameters and options of the wireless
devices are to be programmed by means of the C
ONFIGURATION
function (S
ERVICE MODE
Æ
S
TRUCTURE
Æ
H
ARDWARE
Æ
E
XPANDERS
Æ
S
ETTINGS
Æ
controller name
Æ
C
ONFIGURATION
).
Having started the function, select the zone to which the wireless device is assigned and
press the [#] or
X
key. In case of devices which take up more zones, selection of the suitable
zone depends additionally on the parameter to be programmed. Having programmed the
parameters, confirm the new settings with the [#] key. Automatic return to the zone selection
list will follow.
In the LCD keypad connected to the controller, additional parameters and options of the
wireless devices are also programmed by means of the C
ONFIGURATION
function (S
ERVICE
MODE
Æ
S
ETTINGS
Æ
C
ONFIGURATION
). Having started the function, select the device form the
list and press [#] or
X
. In case of devices which take up more zones, selection of the suitable
zone depends additionally on the parameter to be programmed. Having programmed the
parameters, confirm the new settings with the [#] key. Automatic return to the device
selection list will follow.
Configuration of the wireless devices by means of the LCD keypad of VERSA system is
described in the programming manual for VERSA control panels.
12.2.1 APD-100
detector
The
W
and
X
keys enable navigation between the programmable parameters. The
S
and
T
keys make it possible to select sensitivity within the range from 1 to 3 (see Table 10), as well
as enable/disable the pet immunity option. Enabled pet immunity option is indicated by the
symbol.
12.2.2 APMD-150
detector
The
W
and
X
keys allow you to navigate between the detector programmable parameters,
and the
S
and
T
keys to modify them. The following should be programmed:
– sensitivity of the infrared path within the 1 to 4 range (1 – minimum; 4 – maximum);
– sensitivity of the microwave path within the 1 to 8 range (1 – minimum; 8 – maximum);
– manner of operation in the test mode: 0 (signaling violation after motion is sensed by both
detectors), 1 (signaling violation after motion is sensed by IR detector) or 2 (signaling
violation after motion is sensed by MW detector).
12.2.3 AMD-100
and
AMD-101 detector
Use the
S
and
T
keys to select the active reed switch.
12.2.4 AMD-102
detector
After selecting the first position / the first zone occupied by the AMD-102 detector, use the
S
and
T
keys to indicate the active reed switch.
After selecting the second position / the second zone occupied by the AMD-102 detector, the
parameters of roller shutter zone can be configured. The
W
and
X
keys allow you to navigate
between the parameters, and the
S
and
T
keys to modify them. The following should be
programmed:
– number of pulses within the 1 to 8 range;
– pulse validity: 30, 120 or 240 seconds, or unlimited duration (--- on the display) i.e. only
switching over the detector from passive in to active state will reset the pulse counter.
12.2.5 AGD-100
detector
The
S
and
T
keys enable sensitivity to be selected within the 1 to 3 range (see Table 10).