Chapter 2 Alarm
Handling Procedure
1.
Improve the power supply quality of the equipment room;
2.
If the detected AC voltage value is lower than the threshold value for alarm of AC
voltage being low, then appropriately decrease the threshold value;
3.
Check whether the AC transducer's connection is normal and whether the transducer
has no problem;
4.
Check whether the monitoring unit's socket is inserted properly;
5.
Replace the monitoring unit.
2.1.30 9006 AC Over-Volt
Alarm Property
l
Alarm Code: 9006
l
Alarm Information: The AC input phase voltage is higher than Phase.UnderVolt.
l
Alarm Level: Minor
l
Alarm Type: Equipment Alarm
Sub-code Description
None
Effect on the System
1.
The operation safety of the rectifier is influenced.
2.
The rectifier will automatically power off for protection.
Possible Causes
1.
The AC input voltage is high.
2.
The AC over-voltage value of the monitoring unit is set too low.
3.
The AC transducer's connection is faulty or the transducer is damaged.
4.
The monitoring unit's socket is of bad contact or disconnected.
5.
The monitoring unit is faulty.
Handling Procedure
1.
Improve the power supply quality of the equipment room;
2.
If the detected AC voltage value is higher than the threshold value for alarm of AC
voltage being high, then appropriately increase the threshold value;
3.
Check whether the AC transducer's connection is normal and whether the transducer
has no problem;
4.
Check whether the monitoring unit's socket is inserted properly;
5.
Replace the monitoring unit.