Standard Inverter Specifications
The standard Inverter specifications are listed by capacity in the following tables.
Specifications by Model
Specifications are given by model in the following tables.
200V Class
* 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa motor. When selecting the actual motor and Inverter, be sure that the Inverter's
rated current is applicable for the motor's rated current.
* 2. The startup torque for a 200 V Class Inverter for 110 kW is 120% (low carrier).
* 3. A 3-wire transformer is required on the power supply for 12-phase rectification.
Table 9.1 200 V Class Inverters
Model Number CIMR-F7A
20P4
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
2030
2037
2045
2055
2075
2090
2110
Max. applicable motor output
(kW)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
Rated input current (A)
3.8
4.9
8.4
11.5
18
24
37
52
68
84
94
120
160
198
237
317
381
457
Rated output capacity
(kVA)
1.2
1.6
2.7
3.7
5.7
8.8
12
17
22
27
32
44
55
69
82
110
130
160
Rated output current (A)
3.2
4.1
7.0
9.6
15
23
31
45
58
71
85
115
145
180
215
283
346
415
Max. output voltage (V)
3-phase; 200, 208, 220, 230, or 240 VAC
(Proportional to input voltage.)
Max. output frequency
(Hz)
CT selected (low carrier, constant torque applications): 150 Hz max.
VT selected (high carrier, variable torque applications): 400 Hz max.
Rated voltage (V)
Rated frequency (Hz)
3-phase, 200/208/220/230/240 VAC, 50/60 Hz
Allowable voltage fluctua-
tion
+ 10%, - 15%
Allowable frequency fluc-
tuation
±5%
Measures
for power
supply
harmonics
DC reactor
Optional
Built in
12-phase rec-
tification
Not possible
Possible
*3
O
utp
ut rat
ings
300 Hz max.