4
-6
* 1. The setting range for acceleration/deceleration times will depends on the setting for C1-10. When C1-10 is set to 0, the setting range for acceleration/
deceleration times becomes 0.00 to 600.00 seconds.
* 2. Only 1(VT) can be set for 200 V Class 110 kW as well as 400 V Class 220 kW and 300 kW Inverters.
1
L1-01
Motor protection
selection
Set to enable or disable the motor overload
protection function using the electronic ther-
mal relay.
0: Disabled
1: General motor protection
2: Inverter motor protection
3: Vector motor protection
0 to 3
1
5-55
6-60
IMPORTANT
When C6-01 is set to 0 (CT), non-low noise will apply and the Inverter overload withstand ratio will be
150% of the Inverter rating per minute. When C6-01 is set to 1 (VT), low noise will apply and the Inverter
overload withstand ratio will be 120% of the Inverter rating per minute. If C6-01 is set to 1 (VT) when
overload withstand capability is required by the application, the life of the Inverter may be reduced.
Table 4.2 Constants That Are Set As Required
Constant
Number
Name
Description
Setting Range
Factory
Setting
Page
b1-03
Stopping method
selection
Select stopping method when Stop Com-
mand is sent.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop
3: Coast to stop with timer
0 to 3
*1
0
5-10
6-17
C6-02
Carrier frequency
selection
The carrier frequency is set low if the motor
cable is 50 m or longer or to reduce radio
noise or leakage current. The factory setting
and setting range depends on the setting of
C6-01.
0, 1
(C6-01=0)
0 to F
(C6-01=1)
0, 1
(C6-01=0)
6
*2
(C6-01=1)
5-25
6-2
d1-01 to
d1-04 and
d1-17
Frequency refer-
ences 1 to 4 and
jog frequency ref-
erence
Set the required speed references for multi-
step speed operation or jogging.
0.00 to 400.00
*3*4
d1-01 to
d1-04: 0.00
Hz
d1-17: 6.00
Hz
5-26
6-10
0.00 to 300.00
*3*5
H4-02 and
H4-05
FM and AM termi-
nal output gain
Set the voltage level gain for the multi-func-
tion analog output 1 (H4-02) and 2 (H4-05).
Set the number of multiples of 10 V to be
output as the 100% output for the monitor
item.
0.00 to 2.50
H4-02:
1.00
H4-05:
0.50
5-52
L3-04
Stall prevention
selection during
deceleration
0: Disabled (Deceleration as set. If
deceleration time is too short, a main
circuit overvoltage may result.)
1: Enabled (Deceleration is stopped when
the main circuit voltage exceeds the
overvoltage level. Deceleration restarts
when voltage is returned.)
2: Intelligent deceleration mode
(Deceleration rate is automatically
adjusted so that the Inverter can
decelerate in the shortest possible time.
Set deceleration time is disregarded.)
3: Enabled (with Braking Resistor Unit)
When a braking option (Braking Resistor,
Braking Resistor Unit, Braking Unit) is
used, always set to 0 or 3.
0 to 3
*6
1
5-59
6-32
Table 4.1 Basic Settings of Constants (Continued)
Constant
Number
Name
Description
Setting Range
Factory
Setting
Page