User Constant Tables
5-
85
400 V Class Inverters
Con-
stant
Number
Name
Unit
Factory Setting
-
Inverter Capacity
kW
0.4
0.75
1.5
2.2
3.7
4.0
5.5
7.5
11
15
o2-04
kVA selection
-
20
21
22
23
24
25
26
27
28
29
b8-03
Energy-saving filter time
constant
s
0.50 (Open loop vector control)
b8-04
Energy-saving coeffi-
cient
-
576.40
447.40
338.80
313.60
245.80
236.44
189.50
145.38
140.88
126.26
C6-01
CT/VT selection
-
1
1
1
1
1
1
11
1
1
1
0
0
0
0
0
0
0
0
0
0
C6-02
Carrier frequency selec-
tion (when VT is
selected)
*1 *3
-
6
*2
6
*2
6
*2
6
*2
6
*2
6
*2
6
*2
6
*2
6
*2
6
*2
-
Carrier frequency selec-
tion upper limit (when
VT is selected)
*1
-
6
6
6
6
6
6
6
6
6
6
E2-01
(E4-01)
Motor rated current
A
1.00
1.60
3.10
4.20
7.00
7.00
9.80
13.30
19.9
26.5
E2-02
(E4-02)
Motor rated slip
Hz
2.90
2.60
2.50
3.00
2.70
2.70
1.50
1.30
1.70
1.60
E2-03
(E4-03)
Motor no-load current
A
0.60
0.80
1.40
1.50
2.30
2.30
2.60
4.00
5.6
7.6
E2-05
(E4-05)
Motor line-to-line resis-
tance
W
38.198
22.459
10.100
6.495
3.333
3.333
1.595
1.152
0.922
0.550
E2-06
(E4-06)
Motor leak inductance
%
18.2
14.3
18.3
18.7
19.3
19.3
18.2
15.5
19.6
17.2
E2-10
Motor iron loss for
torque compensation
W
14
26
53
77
130
130
193
263
385
440
L2-02
Momentary power loss
ridethru time
s
0.1
0.1
0.2
0.3
0.5
0.5
0.8
0.8
1.0
2.0
L2-03
Min. baseblock (BB)
time
s
0.1
0.2
0.3
0.4
0.5
0.6
0.6
0.7
0.8
0.9
L2-04
Voltage recovery time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L8-02
Overheat pre-alarm level
°
C
95
95
95
90
95
95
95
90
95
95
N5-02
Motor acceleration time
s
0.178
0.142
0.166
0.145
0.154
0.154
0.168
0.175
0.265
0.244