Writing Constant Set Values Stored in the Digital Operator to the Inverter (COPY)
To write constant set values stored in the Digital Operator to the Inverter, make the settings using the follow-
ing method.
During the copy operation, errors may occur. If an error is displayed, set the constants again. Error displays
and their meanings are shown below. (Refer to
Chapter 7
Errors when Using Digital Operator Copy Func-
tion.)
Table 6.2 COPY Function Procedure
Step
No.
Digital Operator Display
Explanation
1
Press the MENU Key, and select advanced pro-
gramming mode.
2
Press the DATA/ENTER Key, and select the
constants monitor display.
3
Display o3-01 (Copy Function Selection) using
the Increment Key and Decrement Key.
4
Press the DATA/ENTER Key, and select the
constants setting display.
5
Change the set value to 2 using the Increment
Key.
6
Set the changed data using the DATA/ENTER
Key. The COPY function will start.
7
If the COPY function ends normally, End is dis-
played on the Digital Operator. Constant o3-01
is automatically reset to 0, and then the display
returns to o3-01.
Error Display
Meaning
Inverter product code and Inverter software number are different.
Inverter capacity with which you are trying to copy, and the Inverter capacity stored in the Digital
Operator are different.
The Inverter control method in which you are trying to copy, and the Inverter control method stored
in the Digital Operator are different.
Comparison between the constant written to the Inverter and the constant in the Digital Operator
shows they are different.
After copying has ended, comparison between the sum value of the Inverter constant area and the
sum value of the Digital Operator constant area shows they are different.