User Constant Tables
A: Setup Settings
The following settings are made with the environment constants (A constants): Language displayed on the
Digital Operator, access level, control method, initialization of constants.
Initialize Mode: A1
User constants for the environment modes are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
A1-00
Language
selection for
Digital
Operator
display
Used to select the language
displayed on the Digital
Operator (LED).
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
This constant is not initial-
ized by the initialize opera-
tion.
0 to 6
1
Yes
A
A
A
A
100H
-
A1-01
Constant
access level
Used to set the constant
access level (set/read.)
0: Monitoring only
(Monitoring drive mode
and setting A1-01 and
A1-04.)
1: Used to select user
constant
(Only constants set in
A2-01 to A2-32 can be
read and set.)
2: Advanced
(Constants can be read
and set in both quick
programming mode and
advanced programming
(A) mode.)
0 to 2
2
Yes
A
A
A
A
101H
4-17
6-154
A1-02
Control
method
selection
Used to select the control
method for the Inverter
0: V/f control
1: V/f with PG
2: Open loop vector
This constant is not initial-
ized by the initialize opera-
tion.
0 to 2
0
No
Q
Q
Q
Q
102H
4-5
4-7
4-18
0 to 3
3: Flux vector