3
-8
Advanced Programming Mode
In advanced programming mode, all Inverter constants can be monitored and set.
Constants can be changed from the setting displays. Use the Increment, Decrement, and Shift/RESET Keys to
change the frequency. The user constant will be written and the monitor display will be returned to when the
DATA/ENTER Key is pressed after changing the setting.
Refer to
Chapter 5 User Constants
for details on the constants.
Example Operations
Key operations in advanced programming mode are shown in the following figure.
Fig 3.6 Operations in Advanced Programming Mode
Function Selection Display
Monitor Display
Setting Display
Mode Selection Display
MENU
DRIVE QUICK
VERIFYA.TUNE
ADV
DRIVE QUICK
VERIFYA.TUNE
ADV
DRIVE QUICK
VERIFYA.TUNE
ADV
PID control: b5-xx
ESC
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
Setup settings: A1-xx
ESC
ESC
ESC
ESC
Language
ESC
ESC
ESC
RESET
RESET
ESC
PID feedback command
loss detection time
ESC
ESC
PID control mode selection
ESC
ESC
ESC
Proportional gain
ESC
RESET
ESC
Reverse regenerative torque limit
ESC
ESC
Forward torque limit
ESC
ESC
ESC
Reverse torque limit
Copy functions: o3-xx
ESC
RESET
ESC
Read permitted selection
ESC
ESC
Copy function selection
ESC
DRIVE QUICK
VERIFYA.TUNE
ADV
Advanced Programming Mode
Access level
Control mode selection
Torque limits: L7-xx