Wiring Control Circuit Terminals
2-
29
Control Circuit Terminal Connections
Connections to Inverter control circuit terminals are shown in
Fig 2.22
.
Fig 2.22 Control Circuit Terminal Connections
Inverter
CIMR-F7A2022
P2
PC
Open collector 1
Open collector 2
Multi-function
open-collector outputs
48 VDC, 50 mA
P1
Default:
Frequency
agree signal
Default: Zero-
speed
MA
MB
MC
Error contact output
250 VAC, 10 mA min. 1 A max.
30 VDC, 10 mA min. 1 A max.
M1
M2
Multi-function contact output
250 VAC, 10 mA min. 1 A max.
30 DC, 10 mA min. 1 A max.
Default: Running
signal
AC
MP
Pulse train output
Default: Output
frequency
S5
S8
S1
S2
S3
S4
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
Multi-function
contact input
Defaults
IG
MEMOBUS
communications
RS-485/422
R-
R+
S-
S+
Terminating
resistance
FM
AM
Multi-function analog output 1
AC
E(G)
-10 to 10 V 2 mA
AM
FM
+
+
−
−
Default: Output current
0 to +10 V
Default: Output current
0 to +10 V
-10 to 10 V 2 mA
Multi-function analog output 2
Ammeter adjustment
20 k
Ω
Ammeter adjustment
20 k
Ω
+24V 8mA
SC
+24V
CN5 (NPN setting)
S6
S7
Multi-step speed
setting 2
Jog frequency
selection
P
P
4 to 20 mA
0 to 10 V
Pulse train input
RP
+V
A1
A2
AC
0V
Master speed pulse train
Frequency setting power
+15 V 20 mA
Master speed reference
0 to 10 V (20 k
Ω
)
Master speed reference
4 to 20 mA (250
Ω
)
[0 to 10 V (20 k
Ω
) input]
Frequency setting
adjustment
Frequency
setter
2 k
Ω
External
frequency
references
2 k
Ω
2
1
3
E(G)
A3
0 to 10 V
P
-V
(
−
15V 20mA)
MA
MC
4
3
0 to 32 kHz (3 k
Ω
)
High level: 3.5 to 13.2 V
input
0 to 32 kHz (2.2 k
Ω
)
Multi-step command 1
(Main speed switching)
External
baseblock command
for Braking Unit
Thermal switch contact
Shield wire
connection terminal
Multi-function anlog input
0 to 10 V
(20 k
Ω
)
Factory setting:
Not used