Communications Option Boards: F6
User constants for a Communications Option Board are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
F6-01
Operation
selection
after com-
munica-
tions error
Set the stopping method for
communications errors.
0: Deceleration stop using
deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3
1
No
A
A
A
A
3A2H
-
F6-02
Input level
of external
fault from
Communi-
cations
Option
Board
0: Always detect
1: Detect during operation
0 or 1
0
No
A
A
A
A
3A3H
-
F6-03
Stopping
method for
external
fault from
Communi-
cations
Option
Board
0: Deceleration stop using
deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3
1
No
A
A
A
A
3A4H
-
F6-04
Trace sam-
pling from
Communi-
cations
Option
Board
-
0 to
60000
0
No
A
A
A
A
3A5H
-
F6-06
Torque ref-
erence/
torque limit
selection
from opti-
cal option
0: Torque reference/torque
limit from transmission
disabled.
1: Torque reference/torque
limit from transmission
enabled.
0 or 1
0
No
No
No
No
A
3A7H
-
F6-08
Operation
selection
after SI-T
WDT error
Set the stopping method for
SI-T WDT errors (E5).
0: Deceleration stop using
deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3
1
No
A
A
A
A
3B6H
-
F6-09
Number of
SI-T BUS
error detec-
tion
Set the number which SI-T
detects BUS errors.
2 to 10
2
No
A
A
A
A
3B7H
-